Δεν ειναι ακριβώς έτσι. το τι επιτρέπει ο aci και υπό ποιες συνθήκες περιγράφεται στο CHAPTER 6 — FORMWORK, EMBEDDED PIPES, AND CONSTRUCTION JOINTS
6.3 — Conduits and pipes embedded in concrete
6.3.1 — Conduits, pipes, and sleeves of any material
not harmful to concrete and within limitations of 6.3
shall be permitted to be embedded in concrete with
approval of the engineer, provided they are not considered
to replace structurally the displaced concrete,
except as provided in 6.3.6.
6.3.6 — Conduits, pipes, and sleeves shall be permitted
to be considered as replacing structurally in compression
the displaced concrete provided in 6.3.6.1
through 6.3.6.3.
6.3.6.1 — They are not exposed to rusting or other
deterioration.
6.3.6.2 — They are of uncoated or galvanized iron or
steel not thinner than standard Schedule 40 steel pipe.
6.3.6.3 — They have a nominal inside diameter not
over 2 in. and are spaced not less than 3 diameters on
centers.
άρα μιλά μόνο για θλίψη και διαμετρούς μεχρι 5εκ αλλά και γενικά παντού λέει να το αποδείξεις υπολογιστικά αλλά ΚΑΙ να το επιτρέψει ο μηχανικός
edit: Πειράματα και προβλήματα εφαρμογης της τοποθέτησης
1. EXPERIMENTAL STUDY OF REINFORCED CONCRETE COLUMNS CONCEALING RAIN WATER PIPE: http://www.penerbit.utm.my/onlinejournal/43/B/JTDIS43B2.pdf
2. Συμπλήρωμα της άνω δημοσίευσης από τους ιδιους: http://myais.fsktm.um.edu.my/6529/1/A__CRITICAL__REVIEW__OF__THE_REINFORCED_CONCRETE__COLUMNS__AND__WALLS_CONCEALING__RAIN__WATER__PIPE__IN__MULTISTOREY__BUILDINGS.pdf